5.7.9
Multi-functional valve (pressure relief valve):
Figure
5.7.9.1 Default setting for opening pressure of multifunctional valve (MFV)
NOTICE!
The opening pressure (overpressure) of the multifunctional valves (MFV)
is factory-set to 1 MPa (8 bar / 0.8 MPa).
For new installations or replacement of a valve, it must be converted to
0.7 MPa (7 bar). Information on the setting can be found in the operating
instructions of the MFV in chapter on "Overpressure setting".
The operating instructions for the MFV are included in the scope of delivery of
the MFV.
If these are no longer available, please contact the manufacturer: Ecolab
Engineering GmbH.
Material
Connection
PP
Size G 5/8
PVDF
PP
Size G 5/4
PVDF
Misuse
Article no.
TurboPump,
EMP III
54 l/h
EMP III
80 - 120 l/h
55
Installation
EBS No.
249288
10001493
249286
10001171
201539
10025967
201540
10025966
417102267 Ver. 04-11.2023