9 Error Causes and Remedies

9.1 Optical displays

Assignment, see chapter "Bus status display" on page 92.
Link LED
Off
Flashing
On

9.2 Device status - messages, Object 3000h

Assignment, see chapter "Object 3000h: Status" on page 115.
active Bit
0
1
Printed in the Federal Republic of Germany
01/14/2022
Cause
Voltage supply absent or too low
Connector plug not correctly
wired or screwed on
No bus connection
Hardware error,
measuring system defective
Measuring system ready for
operation, connection to master
established, data transfer active.
Measuring system ready for
operation, connection to master
established, no data transfer.
Cause
Number of magnets incorrect
Internal error occurred
TR-ELA-BA-DGB-0020 v04
Remedie
- Check voltage supply, wiring
- Is the voltage supply in the permissible range?
Check wiring and connector plug for correct fitting
Check bus cable
Replace measuring system
-
-
Remedie
- Configurated number of magnets must agree
with the operated number of magnets. Check
settings of Object 2004h: Number of enabled
Sensors, see page 113.
- Are all the magnets located within the
permissible measuring range? Check the
position outputs. See also Object 2005h:
Position value at lost magnet, page 114.
- Shut-off measuring system voltage then switch
on again. If the error recurs despite this
measure, the measuring system must be
replaced.