Parameterization
7.3 Object 0x04, Assembly
The IO Assembly Object returns the cyclic output data of the measuring system.
About the Configuration Assembly the most important attributes can get
parameterized very simple and fast.
Only a static configuration is supported (Static Assembly). Therefore, the number
of the instances and attributes are defined fix and can't be changed.
7.3.1 Common Services
Service Code
0x0E
7.3.2 Class Attributes
No.
Access
Name
1
Get
Revision
2
Get
Max Instance
Number of
3
Get
Instances
4
-
-
5
-
-
Maximum
ID Number
6
Get
Class
Attributes
Maximum ID
Number
7
Get
Instance
Attributes
Table 11: Assembly, Overview of the class attributes
TR-Electronic GmbH 2013, All Rights Reserved
Page 118 of 175
Service Name
Get_Attribute_Single
Data type
Attribute Description
UINT
Revision of this object
Maximum instance number of an
UINT
object currently created in this class
level of the device.
Number of object instances currently
UINT
created at this class level of the
device.
-
not implemented
-
not implemented
The attribute ID number of the last
UINT
class attribute of the class definition
implemented in the device.
The attribute ID number of the last
UINT
instance attribute of the class definition
implemented in the device.
TR-ECE-BA-DGB-0102 v10
Description
Returns the contents of the specified
attribute.
Printed in the Federal Republic of Germany
Default
0x0002
0x0096
0x0007
-
-
0x0007
0x0003
01/27/2022