5. Functional description

The starting signal for the fire pump is given via two redundant
pressure switches. The fire pump can only be switched off
manually.
The control of the fire pump has been arranged in such a way that
motor failures, for example due to heating, do not cause the fire
pump to stop, but only in fault indications and/or a potential-free
signal to a superior fault centre.
In addition to the fire pump, ancillary VdS-approved equipment
can also be controlled.

6. Construction

The control cabinet made of steel sheet is protected against
ingress (IP54). The standard colour of the cabinet is red
(RAL 3000). The mounting plate is made of 3 mm galvanised
sheet steel.
The cabinet design depends on the selected options and the
performance of the fire pump. The dimensions of the control
cabinet depend on the number of options installed and on
whether the controller is wall-mounted or free-standing.
Cables of wall-mounted controllers enter through cable glands.
Cables of free-standing controllers enter a 100 mm high base
frame and a bottom plate split in three parts.

6.1 Control panel

The control panel design depends on the selected options.
The control panel has a number of standard components
(all models) and optional components (selected options).
See fig. 2 and the tables below.
V
A
Fire pump
Fig. 2
CONTROL FS 1 control panel
Standard controls and indicator lights
Description
H1
Horn (acoustic).
H2 White
Pump is running.
Pump is manually switched
H3
Blue
off.
H4
Yellow
Fault.
Voltmeter with phase-
S1
reversing switch.
S2
Pump on.
S3
Pump off.
S4
Horn off.
S5
Indicator light test.
Optional controls and indicator lights
Description
H5
White
Pump is running.
Pump is manually switched
H6
Blue
off.
H7
Yellow
Fault.
S6 Manual/automatic operation.
S8
Pump on.
S7
Pump off.
H8
White
Compressor is running.
Compressor is manually
H9
Blue
switched off.
H10
Yellow
Fault.
S9 Manual/automatic operation.
S11
Compressor on.
S10
Compressor off.
H11 White
Pump is operating.
Pump is manually switched
H12
Blue
off.
H13
Yellow
Fault.
S12 Manual/automatic operation.
S14
Pump on.
S13
Pump off.
Minimum water level
H14 White
(electrode in pressure tank).
Normal water level
H15 White
(electrode in pressure tank).
Maximum water level
H16 White
(electrode in pressure tank).
Minimum water level
H17 White
(float switch).
Maximum water level
H18 White
(float switch).
H19 White
Valve is closed.
H20 White
Valve is open.
H21
Yellow
Fault.
S15
Valve open.
S16
Valve closed.