UBase
OperationStep1
Characterist1
OpMode1
Fortsetzung auf nächster Seite
Applikationshandbuch
trip. By setting t1Min longer than the operation time for other protections such
unselective tripping can be avoided.
ResetTypeCrvn: This parameter can be set: Instantaneous/Frozen time/Linearly
decreased. The default setting is Instantaneous.
tIResetn: Reset time for step n if inverse time delay is used, given in s. The default
value is 25 ms.
kn: Time multiplier for inverse time characteristic. This parameter is used for co-
ordination between different inverse time delayed undervoltage protections.
ACrvn, BCrvn, CCrvn, DCrvn, PCrvn: Parameters to set to create programmable
under voltage inverse time characteristic. Description of this can be found in
the "Technical reference manual".
CrvSatn: When the denominator in the expression of the programmable curve is
equal to zero the time delay will be infinity. There will be an undesired
discontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval U> up to U>·(1.0 + CrvSatn/100) the used
voltage will be: U>·(1.0 + CrvSatn/100). If the programmable curve is used this
parameter must be calculated so that:
CrvSatn
×
-
>
B
C
100
EQUATION1448 V1 DE
HystAbsn: Absolute hysteresis set in % of UBase. The setting of this parameter is
highly dependent of the application. If the function is used as control for automatic
switching of reactive compensation devices the hysteresis must be set smaller than
the voltage change after switching of the compensation device.
Einstellparameter
Einheit
Aus
-
Ein
0.05 - 2000.00
kV
Aus
-
Ein
UMZ
-
AMZ-Kennlinie A
AMZ-Kennlinie B
AMZ-Kennlinie C
Prog. AMZ-Kennl.
1 aus 3
-
2 aus 3
3 aus 3
0
Stufe
Standard
-
Aus
0.05
400.00
-
Ein
-
UMZ
-
1 aus 3
Abschnitt 4
IED Anwendung
(Gleichung 334)
Beschreibung
Funktion Ein / Aus
Bezugsspannung
Freigabe Betrieb Stufe 1
Auswahl der Auslösekennlinie für die Stu‐
fe 1
Anzahl der Phasen bei denen der An‐
sprechschwellwert für eine Auslösung
überschritten sein muss (1 aus 3, 2 aus
3, 3 aus 3) für die 1. Stufe