ABB RED670 Handbuch Seite 202

Längsdifferentialschutz
Vorschau ausblenden Andere Handbücher für RED670:
Inhaltsverzeichnis

Werbung

Abschnitt 4
IED Anwendung
198
Where:
Vph
is phase to earth voltage at the relay point
Iph
is phase current in the faulty phase
3I0
is earth fault current
Z1
is positive sequence impedance
Z0
is zero sequence impedance
A
IEC05000221 V1 DE
Abb. 87:
Class 1, parallel line in service.
The equivalent circuit of the lines can be simplified, see figure 88.
Z0
A
Z0
B
IEC99000038 V1 DE
Abb. 88:
Equivalent zero sequence impedance circuit of the double-circuit,
parallel, operating line with a single phase-to-earth fault at the
remote busbar.
When mutual coupling is introduced, the voltage at the relay point A will be
changed according to equation 98.
æ
=
×
+
Vph
Z1
Iph 3 I0
ç
L
è
EQUATION1276 V1 DE
By dividing equation
98
the impedance present to the relay at A side as:
Z0m
Z<
Z<
-
Z0
m
-
Z0
m
-
Z0
Z1
L
L
×
+
3 I0p
×
3 Z1
L
by equation
97
and after some simplification we can write
1MRK 505 186-UDE B
B
en05000221.vsd
Z0 m
C
99000038.vsd
ö
Z0
m
÷
×
3 Z1
ø
L
Applikationshandbuch
(Gleichung 98)