8.6 CT Connection and Phase instruction
WARNING!
Risk of electric shock!
If the device is connected by unqualified persons,
there is a risk of life-threatening electric shock!
The CT connection may only be carried out by a
suitably qualified electrician in compliance with the
applicable regulations and standards!
The current transducers (CT) are used for monitoring
electricity consumption throughout the house.
At the meantime, the inverter will also need the data
from the current transducer for the grid-feed-in.
The installation / connection of the current transducers is essential
for the fault-free operation of the inverter.
Proceed as described below.
CT connection steps for the installer
  ATTENTION!
Risk of malfunction!
Incorrect installation of the measuring transducer
can lead to massive problems during operation
of the system!
Follow the instructions below exactly!
Attach the 3 current transducers to the outer conductor (L)
connected to the inverter, as shown in the following
connection diagram (next page)
Position them as close as possible to the meter,
so that there is no cable outlet between
the current transducers and the electricity meter.
Connecting the Device
97