Connecting the Device
8.4 EPS connection
  WARNING!
Risk of electric shock!
If the device is connected by unqualified persons,
there is a risk of life-threatening electric shock!
EPS connection and grounding may only be carried out by a
suitably qualified electrician in compliance with the
applicable regulations and standards!
The inverter has on and off grid function,
i.e. if the grid is available, the hybrid inverter supplies
backup 1 and 2 with power.
If the grid is not available, Backup 1 is supplied
with power as a priority.
The supply to backup 2 can be set as desired.
When there is a power outage
or when there is no power grid available:
• If there is no battery report,
the inverter will supply power to both BACKUP1 and BACKUP2.
• If there is a battery report,
the inverter only supplies power to BACKUP1.
Requirements for the EPS connection
• Observe the following recommendations
for cable and micro -breaker:
Cable and micro-breaker
recommendations for the EPS connection
EPS cable
EPS micro-breaker
90
4 - 6 mm
2
20 A