Gridconnectionstepsfortheinstaller
• Check the grid voltage and compare it with the per-
missible voltage range (see "Technical data").
• Disconnect the circuit board from all phases and
secure it against possible reconnection.
• Remove the waterproof lid from the grid port
on the inverter (1).
• Make the AC lines as follows:
• Select a suitable cable (Refer to the corresponding
table in the previous section).
• Remove 10 mm of the insulation from the end of the
cable (2).
• Clamp the connections with crimping pliers.
• Disassemble the waterproof connectors and the
waterproof covers and pass the cable through the
waterproof connector (3).
• Connect the AC connection to the "Grid" port
of the inverter using a slotted screwdriver (4).
  WARNING!
Risk of electric shock due to damage!
Be careful not to apply too much torque
when connecting with the screwdriver
to avoid damage to the feed-through terminals
and a resulting risk of electric shock.
The limit load when connecting the AC termi-
nals is 1.2 Nm.