Unit menu
Configuration
point
Ch. X source temp.
KT X temp. signal
type
Ch. X temp.
connection type
10.3.2
Versatronic Cooling Water
This table applies only for Ci or Cr measurement in the cooling water configuration (see
Ä Chapter 5.2 'Material code' on page 17 )
Configuration
point
KT X designation
KT X W-
KT X hyst. W +
KT X hyst. Ws
Configuration point Selection/configuration
KT X dos.duration bioc.
1
KT X dos.duration bioc.
2
(C1 and CB only) *
KT X exposure
KT X time pre-
circulation
* = see
Ä Chapter 5.2 'Material code' on page 17
417102279 Rev. 4-07.2023
Selection/configuration
Analogue inputs
/*IN4-temperature input 1
*IN5 temperature input 2
......IN11 universal input. 2
uncomp.*IN11
Universal input 2 comp.
IN12 universal input 3 uncomp.
* IN12 universal input 3 comp.
* = please only select the marked points!
PT100
PT1000
2-wire
3-wire
Selection/configuration
Text box
Number field
Range: - 99999–99999
Number field
Range: - 99999–99999
Number field
Range: - 99999–99999
Hours/minutes/seconds
(hh: mm: ss)
Range: 0-23: 0-59: 0-59
Hours/minutes/seconds
(hh: mm: ss)
Range: 0-23: 0-59: 0-59
Hours/minutes/seconds
(hh: mm: ss)
Range: 0-23: 0-59: 0-59
Hours/minutes/seconds
(hh: mm: ss)
Range: 0-23: 0-59: 0-59
Explanation
Determination of source
for the temperature
display and temperature
compensation of the
respective channel.
With this selection, it
is possible to use the
temperature signal of
another channel for the
display and temperature
compensation of this
channel.
Selection of type of
temperature sensor and
thus the type of
temperature signal
Selection of connection
type for temperature
sensor
Explanation
Change channel X description
Select lower switching point W-
(W is not met = bleeding off)
Select upper switching point W + as
positive hysteresis of W-
(W + W + = hysteresis + W)
(W+ exceeded = bleeding on)
Select switching point for the
pre-bleeding Ws as a positive
hysteresis of W-
(W + hysteresis Ws = Ws)
(Ws exceeded + dosing time for
biocide = pre-bleeding on)
Explanation
Determine metering time for
metering of biocide 1
Determine metering time for
metering of biocide 2
Determine exposure time
(time for which bleeding remains
locked after completion of biocide.)
Set time for precirculation
(how long circulation is to run
after activation of the circulation
pump before the biocide dose is
released.)
52
Default
Channel 1: IN4
Channel 2: IN5
Channel 3: IN11 comp.
Channel 4: IN12 comp.
PT1000
2-wire
Default
Description
1600 µS/cm
200 µS/cm
(W+ = 1800 µS/cm)
100 µS/cm
(Ws = 1700 µS/cm)
Default
00:00:10
00:00:10
00:00:10
00:00:10

Werbung