3. General information

These installation and operating instructions apply to NKF pumps
with the following approvals or according to the following
standards:
VdS approval
EN standard
DBI standard
CNBOP approval
PAVUS approval
BMOKF approval.
The document also includes the basic information needed for
operating the complete Fire NKF pump set consisting of pump,
controller and electric motor or diesel engine.
See also installation and operating instructions for the controller
and motor or engine.
Fire NKF pump sets according to VdS must be
installed, operated and maintained according to
VdS guidelines. Installation, maintenance and
Note
repair must be carried out by qualified personnel
certified by the German VdS Schadenverhütung
GmbH.

4. Applications

Grundfos NKF pumps and Fire NKF pump sets are designed for
firefighting applications for supplying water to hose reels, fire
hydrants or sprinkler systems. They must not be used for ordinary
pumping of liquids or pressure boosting.
The control cabinet must not be used to supply voltage to other
devices.
Warning
The pumps and pump sets must only be used for
the applications mentioned. Any other use is
considered improper. Grundfos cannot be held
responsible for damage caused by improper use.
The risk is carried solely by the operator.

5. Delivery and storage

5.1 Pump

5.1.1 Delivery
The pumps are delivered from factory in an open or a closed
wooden box designed for transport by forklift truck or a similar
vehicle.
Secure the pump during transport to reduce
Caution
vibrations and/or prevent damage to the shaft
and seal. Do not lift the pump by the shaft.
Lifting the pump by means of a crane
Fig. 1
All manuals and user guides at all-guides.com
5.1.2 Storage
Apply an antirust agent on all non-coated machined surfaces.
If the pump is to be stored for more than six months before start-
up, the inner pump components must be treated with an antirust
agent.
The antirust agent must meet these requirements:
In order to prevent water, dust, etc. from entering the pump, all
openings must be covered until pipes are connected. If not, it will
be very expensive to dismantle the pump to remove foreign
matter after installation.
Turn the pump shaft manually once a month to prevent the shaft
seal from seizing up. The driver must be isolated from the pump.
See service instructions for the pump.

5.2 Pump set

5.2.1 Delivery
The pump set is delivered from factory in an open or a closed
wooden box designed for transport by forklift truck or a similar
vehicle.
5.2.2 Storage
See also installation and operating instructions for the driver.
It must not attack rubber parts.
It must be easy to remove.
It must be applied in accordance with the manufacturer's
instructions.
Observe the safety instructions in the installation
Note
and operating instructions of the individual
components.
Warning
Lift the pump set by means of the lifting eyes of
the base frame. Never use the lifting eyes of the
individual components.
The lifting point should always be above the
centre of gravity of the pump set. See fig. 2.
Alternatively, a forklift truck can be used.
Use only lifting equipment in proper condition.
Lock the cabinet door before moving the pump
set.
Lifting the complete pump set
Fig. 2
Caution
The pump set must be stored in a frost-free room.