5.6.1 Connection of two sensors
The sensor signal is copied to the other pump through the red
wire of the communication cable.
If, optionally, two sensors are connected (one sensor to each
terminal box), cut the red wire. See fig. 21.
Master end
White label
Fig. 21 Elimination of copied sensor signal
5.6.2 Elimination of "alternating operation" and
"standby operation"
If "alternating operation" and "standby operation" are not desired,
but the copied sensor signal (one sensor signal to two pumps) is
desired, cut the green wire. See fig. 22.
Master end
White label
Fig. 22 Elimination of "alternating operation" and
"standby operation"
5.6.3 Elimination of TPED function
If "alternating operation" and "standby operation" as well as the
copied sensor signal are not desired, remove the communication
cable completely.
18
ГК Водная техника info@water-technics.ru (495) 771 72 72 www.water-technics.ru
Интернет-магазин info@wtpump.ru (499) 937 50 61 (800) 505 78 67 www.wtpump.ru
Slave end
Jumper
Slave end
Jumper

6. Modes

Grundfos E-pumps are set and controlled according to operating
and control modes.

6.1 Overview of modes

Operating modes
Normal
Control modes
Uncontrolled
Constant
curve
1) In this example the pump is equipped with a differential
pressure sensor. The pump may also be equipped with e.g.
a temperature sensor in which case the description would be
constant temperature in control mode controlled.

6.2 Operating mode

When the operating mode is set to Normal, the control mode can
be set to controlled or uncontrolled. See section
mode.
The other operating modes that can be selected are Stop, Min. or
Max.
Stop:
The pump has been stopped.
Min.:
The pump is operating at its minimum speed.
Max.: The pump is operating at its maximum speed.
Figure
23
is a schematic illustration of min. and max. curves.
H
Min.
Fig. 23 Min. and max. curves
The max. curve can for instance be used in connection with the
venting procedure during installation.
The min. curve can be used in periods in which a minimum flow is
required.
If the power supply to the pump is disconnected, the mode setting
will be stored.
The remote control R100 offers additional possibilities of setting
and status displays. See section
Stop
Min.
Max.
Controlled
Constant
1)
pressure
6.3 Control
Max.
Q
8. Setting by means of
R100.