needed.
9.
Description of malfunctions and malfunction repair
Table 9.1: Error description / Error handling
Status
LED
Error
on Slave
Backwater in drain
Backwater in drain
Leak on sensor
Temperature flushing
switched off during
runtime
Volume flushing
switched off during
runtime
"Flow with closed valve
detected"
"No flow detected
although valve is open"
PT1000 value too high
PT1000 value too low
Real-time clock data
inconsistent
Manual KHS Mini System Control MASTER
instruction.
You
find
or with the PC-software itself.
Error description / Error handling
Potential cause
General error
Drain is clogged or cannot accept the
flushing volume.
Float switch on the drain has a cable
break
Pipe failure, moisture on the sensor
Medium did not reach the switch-off
temperature in the set time
Set volume not reached
Flow is detected by the vortex flow
sensor with the valve closed
No flow is detected during a flushing
process.
Sensor defective / No sensor available
Sensor defective / No sensor available
Data in the clock are not consistent
this
manual
on
Measures
Check the drain channel,
channel acceptance
capacity.
Replace cable / switch
Check the local area and
remove the moisture
Check the installation
setup and the maximum
flushing time.
Check the installation
setup and the maximum
flushing time.
Check the functioning of
the flush valve
Check the flushing line and
the flushing valve
Replace sensor / Check
inputs on the MASTER
Replace sensor / Check
inputs on the MASTER
Check the time & date and
adjust if necessary. Check
battery/replace if
applicable
38
our
website
Impact
Error message!
Defective control will be
completely blocked
Error message!
Defective control will be
completely blocked
The safety valve is blocking
the system.
Error message!
Temperature operating mode
is blocked in the defective
control.
Error message!
Volume operating mode is
blocked in the defective
control.
Error message! The involved
valve is blocked.
Error message! The involved
valve is blocked.
Error message!
Temperature flushing
operating mode is blocked in
the defective control.
Error message!
Temperature flushing
operating mode is blocked in
the defective control.
All time-based services are
running on false time/date.