General settings:
Para-
Parameter name
meter
P1.1
AUT. SWITCHOVER
SUMMER / WINTER
P1.2
AVERAGE OUTDOOR
TEMP. FOR SUMMER /
WINTER SWITCHOVER
P1.3
OUTDOOR TEMP. FOR
ACTIVATION OF FROST
PROTECTION
P1.4
REQUESTED ROOM
TEMP. WHEN HEATING IS
SWITCHED OFF
P1.5
TEMPERATURE ROUND
UP
P1.6
AUT. SHIFT OF CLOCK
TO SUMMER / WINTER
TIME
P1.7
PERIOD OF TEMPERAT.
LOGGING
P1.8
TONES
P1.9
ADVANCED DISPLAY OF
TEMPERATURES
Settings for the first heating circuit:
Para-
Parameter name
meter
P2.1
HEAT CURVE STEEP-
NESS
P2.2
PARALLEL SHIFT OF
HEATING CURVE
P2.3
DURATION OF BOOST
HEATING
P2.4
ROOM TEMPERATURE
INCREASE BY BOOST
HEATING
Service setting manual
Parameter description
Automatic switch-off and switch-on of heating in respect to
average one-day outdoor temperature.
Setting of average one-day outdoor temperature at which
the heating should switch-off or switch-on.
Setting of outdoor temperature by which the frost protec-
tion will activate and run boiler at minimum temperature.
Setting of requested room temperature when heating is
switched off.
Precision of displayed temperatures.
With the help of a calendar, the controller carries out the
automatic clock changeover between summer and winter
time.
By setting this field you define how often the measured
temperatures are saved.
By setting this field you define whether key pressing is
accompanied with sound signals or not.
Advanced display of temperatures displays temperatures
on main screen in double rows. First row is measured
temperature; second row is required or calculated
temperature.
Parameter description
Heating curve steepness indicates what temperature is
required for the heating bodies by a determined outdoor
temperature.
See chapter Heating curve.
Setting of parallel shift of heating curve or calculated
stand-pipe temperature.
Use this setting to eliminate deviation between actual and
required room temperature.
Duration of boosted room temperature by changeover
from night to day heating period.
Boost room temperature increase by changeover from
night to day heating period.
36
Setting range
Default
setting
0- NO
1
1- YES
10 ÷ 30 °C
18
-30 ÷ 10 °C
-10
2 ÷ 12 °C
6
0- 0.1 °C
1- 0.2 °C
2
2- 0.5 °C
3- 1 °C
0- NO
1- YES
1
1 ÷ 30 min
5
0- OFF
1- KEYPAD
2- ERRORS
1
3- KEYPAD &
ERRORS
0- NO
1- YES
1
Setting range
Default
setting
0,2 ÷ 2,6
0,7 - floor
1,0 - radia-
tors
-15 ÷ 15 °C
0
0 ÷ 200 min
0
0 ÷ 8 °C
3