OEG KSF-Pro Handbuch Seite 37

Kesselschaltfeld
Vorschau ausblenden Andere Handbücher für KSF-Pro:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Settings for the second heating circuit:
Para-
Parameter name
meter
P3.1
HEAT CURVE STEEP-
NESS
P3.2
PARALLEL SHIFT OF
HEATING CURVE
P3.3
DURATION OF BOOST
HEATING
P3.4
ROOM TEMPERATURE
INCREASE BY BOOST
HEATING
P3.5
HEAT CURVE STEEP-
NESS FOR ADDITIONAL
DIRECT CIRCUITS
P3.6
PARALLEL SHIFT OF
HEATING CURVE FOR
ADD. DIRECT CIRCUITS
Settings for domestic hot water:
Para-
Parameter name
meter
P4.1
D. H. W. TEMPERATURE
IN OFF PERIOD
P4.2
PRIORITY OF D. H. W.
WARMING TO CIRCUIT 1
P4.3
PRIORITY OF D. H. W.
WARMING TO CIRCUIT 2
P4.7
TIME PROGRAM FOR D.
H. W. CIRCULATION
P4.8
RUNNING TIME FOR
D. H. W. CIRCULATION
PUMP
Parameter description
Heating curve steepness indicates what temperature is
required for the heating bodies by a determined outdoor
temperature.
See chapter Heating curve.
Setting of parallel shift of heating curve or calculated
stand-pipe temperature.
Use this setting to eliminate deviation between actual and
required room temperature.
Duration of boosted room temperature by changeover
from night to day heating period.
Boost room temperature increase by changeover from
night to day heating period.
Setting of heat curve steepness for additional direct
heating circuits.
Parallel shift of heating curve for additional heating
circuits.
Values 16 ÷ 90 set directly the boiler temperature when
additional direct heating circuit is activated.
Parameter description
Setting of d. h. w. temperature in OFF program timer
interval.
Setting if d. h. w. heating has priority to room heating in
circuit 1.
Setting if d. h. w. heating has priority to room heating in
circuit 2.
Selection of d. h. w. warming time program which will be
used for d. h. w. circulation.
Setting 1 is first time program for domestic hot water
warming.
Setting 2 is second time program for domestic hot eater
warming.
Setting 3 is selected time program for domestic hot water
warming.
Setting of running time for d. h. w. circulation pump. Pump
running period is always followed by the pump stand-by
period.
37
Setting range
Default
setting
0,2 ÷ 2,6
0,7- floor
1,0- radia-
tors
-15 ÷ 15 °C
0
0 ÷ 200 min
0
0 ÷ 8 °C
3
0,2 ÷ 2,6
1,2
-15 ÷ 15 °C
16 ÷ 90 °C
6
Setting range
Default
setting
4 ÷ 70 °C
4
0- NO
1- YES
0
0- NO
1- YES
0
1- PROG. 1
2- PROG. 2
3- SELECT.
PROG.
3
0 ÷ 600 sec
300
Service setting manual