LOCKING BUTTONS
By locking keys, we limit or disable undesired settings or activation of
functions. Buttons are locked by pressing the button
and unlocked by pressing the button
Parameter S1.10 determines the extent of locking buttons:
S1.10=0 - no lock,
S1.10=1 - type of operation for rooms and sanitary water is locked,
S1.10=2 - same as 1, but adds the lock of Party, Eco, d.h. w., and
Fireplace functions.
S1.10=3 - same as 2, but adds the lock of desired temperatures,
S1.10=4 - same as 3, but adds the lock of browsing of info displays and
additional service settings.
When the buttons are locked, the symbol
basic display.

FACTORY SETTINGS - RESET

By pressing the button for 40 seconds, parameters in groups P1,
P2 and S1 are restored to factory settings. Factory settings in table of
parameters are marked with bold text.

ERROR DESCRIPTION

Room sensor error.
If parameter S1.2=1, the built-in sensor contains the fault.
If parameter S1.2=2, the auxiliary sensor contains the fault.
Check type and connection of auxiliary sensor.
If parameter S1.2=3, the built-in or the auxiliary sensor
contains the fault. Check type and connection of auxiliary
sensor. If the error is not fixed, room unit should be sent
to service.
22 English
for 10 seconds,
for 10 seconds.