Herunterladen Inhalt Inhalt Diese Seite drucken

OEG KSF-Pro Handbuch Seite 52

Kesselschaltfeld
Vorschau ausblenden Andere Handbücher für KSF-Pro:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Para-
Parameter name
meter
S6.6
OPERATION OF LIQUID
FUEL BOILER
S6.7
CIRCUITS WITH DE-
LAYED ACTIVATION OF
LIQUID FUEL BOILER
S6.8
SOLAR PUMP KICK
FUNCTION
S6.9
RESPECT MIN. TEMPE-
RATURE OF COLLEC-
TORS OR SOLID FUEL
BOILER
S6.10
OPERATION MODE OF
COLLECTORS OR SOLID
FUEL BOILER CIRCULA-
TION PUMP
S6.11
MINIMUM RPM FOR
PUMP
S6.12
FULL-RPM RUNNING
TIME OF COLLECTORS
OR SOLID FUEL BOILER
CIRCULATION PUMP
S6.13
LOCATION OF COLD
SENSOR FOR DIFF.
THERMOSTAT
S6.14
HEAT PUMP- OPERATION
MODE
S6.15
HEAT PUMP - MAX.
SUPPLY WATER TEMPE-
RATURE
S6.16
HEAT PUMP - OPERATI-
ON HYSTERESIS
S6.17
HEAT PUMP - MIN. OUT-
DOOR TEMP. FOR HEAT
PUMP OPERATION
Service setting manual
Parameter description
Setting if d. h. w. warming with oil boiler and solar collec-
tors or solid fuel boiler can operate at the same time or
oil boiler shall activate with delay after warming with solar
collectors or solid fuel boiler has been stopped.
Selection of circuits where oil boiler shall activate with de-
lay after warming with solar collectors or solid fuel boiler.
1- domestic hot water
2- heating circuits
3- domestic hot water and heating circuits
Special algorithm activates the solar pump to switch
-on for short intervals. This way realistic temperature of
collectors is obtained. This function is used especially with
vacuum (tube) collectors or with classic collectors if the
sensor is fitted outside of the collector body.
We define whether and how the minimum collector or
solid fuel boiler temperature is respected.
Setting of circulation pump ON/OFF or RPM operation
mode. RPM modulation of the pump is done with 5 stages
(40 %, 55 %, 70 %, 85 %, 100 % RPM).
Minimum RPM stage for modulation of circulation pump.
1- 40 % RPM
2- 55 % RPM
3- 70 % RPM
When the differential condition is fulfilled, the circulation
pump runs at max. RPM for a setted time. Afterwards the
pump is running with RPM modulation (if enabled with
parameter S6.10=1).
Cold sensor (T8) place of mount, if it is being used for
differential thermostat. In exact we define storage device
which is being warmed with solar collectors or solid fuel
boiler.
Setting if heat pump should operate in ON/OFF or wea-
ther compenstaed mode.
Setting of max. heat pump output temperature when
operating in weather compenstaed mode.
Setting of hysteresis for heat pump operation.
Setting of min. outdoor temperature below which the heat
pump should switch off.
52
Setting range Default
setting
-1- PARALELL
0 ÷ 600 MIN-
DELAY OF
120
LIQUID FUEL
BOILER
1- D. H. W.
2- CIRCUITS
3- BOTH
1
0- NO
1- YES
0
0- NO
1- YES
2
2- YES,
SWITCH-ON
0- ON/OFF
1- RPM
1
1- 40 %
2- 55 %
1
3- 70 %
5 ÷ 300 s
20
1- D. H. W.
TANK
1
2- HEAT AC-
CUMULATOR
1- ON/OFF
2- WEATHER
2
COMPENSA-
TED
40 ÷ 70 °C
50
2 ÷ 10 °C
4
-30 ÷ 20 °C
-10

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis