10.99
Number / Alarm
Cause
A084
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
The telegram traffic between the DP master
and the CBP has been interrupted (e.g. cable
break, bus cable pulled out or DP master
powered down).
Consequence:
If P722 (P695) is not equal to zero, this will
cause the fault message F082 to be tripped.
A085
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
The CBP does not generate this alarm!
A086
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
Failure of the heart-beat counter on the basic
unit. The heartbeat counter on the basic unit is
no longer being incremented. The
communication between the CBP and the
basic board is disturbed.
A087
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
Fault in the DPS manager software of the
CBP.
A088
See user manual for CB board
CB alarm
A089
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A81 of the 1st CB board
A090
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A82 of the 1st CB board
A091
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A83 of the 1st CB board
A092
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A84 of the 1st CB board
A093
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A85 of the 1st CB board
A094
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A86 of the 1st CB board
A095
Alarm of the 2nd CB board. Corresponds to
A87 of the 1st CB board
CB alarm
See user manual for CB board
A096
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A88 of the 1st CB board
A097
See user manual for TB board
TB alarm 1
not Compact PLUS