10.99
Number / Fault
Cause
F065
No telegram has been received at an SCom
interface (SCom/USS protocol) within the
SCom telegram failure
telegram failure time.
F070
A fault has occurred during initialization of the
SCB board.
SCB initialization fault
F072
A fault has occurred during initialization of the
EB board.
EB initialization fault
F073
4 mA at analog input 1, slave 1 fallen short of
AnInp1SL1
not Compact PLUS
F074
4 mA at analog input 2, slave 1 fallen short of
AnInp2 SL1
not Compact PLUS
F075
4 mA at analog input 3, slave 1 fallen short of
AnInp3 SL1
not Compact PLUS
F076
4 mA at analog input 1, slave 2 fallen short of
AnInp1 SL2
not Compact PLUS
F077
4 mA at analog input 2, slave 2 fallen short of
AnInp2 SL2
not Compact PLUS
F078
4 mA at analog input 3, slave 2 fallen short of
AnInp3 SL2
not Compact PLUS
Siemens AG
6SE7087-6JD50
SIMOVERT MASTERDRIVES
Operating Instructions
Counter-measure
Fault value r949:
1 = Interface 1 (SCom1)
2 = Interface 2 (SCom2)
Check the connection of PMU -X300 or X103 /
27,28 (Compact, chassis unit)
Check the connection of X103 or X100 / 35,36
(Compact PLUS unit)
Check "SCom/SCB TlgOff" P704.01 (SCom1)
or P704.02 (SCom2)
Fault value r949:
1: Board code incorrect
2: SCB board not compatible
5: Error in configuration data
6: Initialization timeout
7: SCB board double
10: Channel error
Fault value r949:
2: 1st EB1 not compatible
3: 2nd EB1 not compatible
4: 1st EB2 not compatible
5: 2nd EB2 not compatible
21: Three EB1 boards
22: Three EB2 boards
110: Fault on 1st EB1
120: Fault on 2nd EB1
210: Fault on 1st EB2
220: Fault on 2nd EB2
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 4, 5.
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 7, 8.
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 10, 11.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 4, 5.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 7, 8.
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 10, 11.