Faults and Alarms
Number / Fault
Cause
F053
After changes have been made to parameters,
a fault has occurred during the calculation of
Parameter fault in
dependent parameters.
follow-up task
F054
A fault has occurred during initialization of the
encoder board.
Encoder board
initialization fault
F056
Communication on the SIMOLINK ring is
disturbed.
SIMOLINK telegram
failure
F058
A fault has occurred during the processing of a
parameter task.
Parameter fault
Parameter task
F059
A fault has occurred in the initialization phase
during the calculation of a parameter.
Parameter fault after
factory setting/init.
F060
Is set if parameter P070 is at zero when
INITIAL LOADING is exited.
MLFB is missing during
initial loading
F061
A parameter which has been entered during
drive setting is in the non-permissible range.
Incorrect
parameterization
F063
The synchronization or positioning technology
functions have been activated without an
PIN is missing
authorization being present (PIN)
12-6
Counter-measure
No remedy
Fault value r949:
1: Board code is incorrect
2: TSY not compatible
3: SBP not compatible
4: SBR not compatible
5: SBM not compatible
6: SBM initialization timeout
7: Board double
20: TSY board double
21: SBR board double
23: SB board three-fold
24: SBP board three-fold
30: SBR board slot incorrect
31: SBM board slot incorrect
32: SBP board slot incorrect
40: SBR board not present
41: SBM board not present
42: SBP board not present
50: Three encoder boards
60: internal fault
- Check the fiber-optic cable ring
- Check whether an SLB in the ring is without
voltage
- Check whether an SLB in the ring is faulty
- Check P741 (SLB TlgOFF)
No remedy
The number of the inconsistent parameter is
indicated in fault value r949. Correct this
parameter (ALL indices) and switch voltage off
and on again. Several parameters may be
affected, i.e. repeat process.
Enter correct MLFB after acknowledging the
fault (power section, initial loading)
The number of the inconsistent parameter is
indicated in fault value r949 (e.g. motor
enocder = pulse encoder in the case of
brushless DC motors) -> correct this
parameter.
- Deactivate synchronization or positioning
- Enter the PIN (U2977)
6SE7087-6JD50
Operating Instructions
SIMOVERT MASTERDRIVES
10.99
Siemens AG