Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMOVERT MASTERDRIVES Motion Control Betriebsanleitung Seite 191

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

10.99
Designation
Order number 6SE70...
Rated voltage
Input
Output
Rated frequency
Input
Output
Rated current
Input
Output
DC link voltage
[kVA] 22.4...27.1 24.7...29.9 30.9...37.4 38.8...47.0 47.4...57.4
Rated output
Aux. power supply
Pulse frequency
[kHz]
Load class II to EN60146-1-1:
Base load current
Overload current
Cycle time
Overload duration
Losses, cooling, power factor
Power factor
Line cosϕ1N
Converter cosϕU
Efficiency η
Pulse frequency 5 kHz
Dissipated losses
[kW]
Pulse frequency 5 kHz
Cooling air required
[m³/s]
Sound pressure level, dimensions, weights
Sound pressure level [dB(A)]
Type of construction
Width
Height
[mm]
Depth
Weight
NOTE
Siemens AG
6SE7087-6JD50
SIMOVERT MASTERDRIVES
23-4EC51
23-8ED51
[V]
[Hz]
[A]
37.4
41.3
34.0
37.5
[V]
[V]
DC 24 (20 -30) (2.0 A without options; more with options)
> 0.98
> 0.98
< 0.92 ind.
< 0.92 ind.
0.98
0.97
0.59
0.70
0.028
0.054
60
65
C
D
180
270
600
600
350
350
[kg]
21
32
Table 11-2
Technical data
Complete fulfillment of the degree of
protection IP20 in accordance with
EN 60529 is dependent on how many
incoming and outgoing control cables
cover the opening area on the lower
section of the unit. If degree of
protection IP20 also has to be met in
operation, the opening may have to be
subsequently reduced.
Operating Instructions
Value
24-7ED51
26-0ED51
3 AC 380 to 480 (-15 % / +10 %)
3 AC 0 ... rated input voltage x 0.86
50/60 ± 6 %
0 ... 400
51.7
64.9
47.0
59.0
510 ... 650
5.0 – 10.0
0.91 x rated output current
1.6 x rated output current
300 s
30 s
> 0.98
> 0.98
< 0.92 ind.
< 0.92 ind.
0.98
0.98
0.87
1.02
0.054
0.054
65
65
D
D
270
270
600
600
350
350
32
32
Technical Data
27-2ED51
79.2
72.0
> 0.98
< 0.92 ind.
0.98
1.27
0.054
65
D
270
600
350
32
11-3

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis