Parameter reset to factory setting

P053 = 6
P060 = 2
P366 = ?
P970 = 0
Unit carries out parameter
reset and goes into status
5 "Drive setting".
Siemens AG
6SE7087-6JD50
SIMOVERT MASTERDRIVES
The factory setting is the defined initial state of all parameters of a unit.
The units are delivered with this setting.
You can restore this initial state at any time by resetting the parameters
to the factory setting, thus canceling all parameter changes made since
the unit was delivered.
The parameters for defining the power section and for releasing the
technology options and the operating hours counter and fault memory
are not changed by a parameter reset to factory setting.
Parameter number
P070
P072
P073
P366
Table 8-3
Parameters which are not changed by the factory setting
Grant parameter access
6: Parameter changes permitted via PMU and serial interface
SCom1 (OP1S and PC)
Menu selection "Fixed settings"
Select desired factory setting
0: Standard
Note:
This parameter was correctly set prior to despatch of
the unit and only needs to be changed in exceptional
cases.
Start parameter reset
0: Parameter reset
1: No parameter change
Fig. 8-4
Sequence for parameter reset to factory setting
Operating Instructions
Parameter name
Order No. 6SE70..
Rtd Drive Amps
Rtd Drive Power
Select FactSet
Parameterization
8-9