Parameterization
8.6

Parameter reset to factory setting

P053 = 6
P060 = 2
P366 = ?
P970 = 0
Unit carries out parameter
reset and then leaves the
"Fixed settings" menu.
8-26
The factory setting is the defined initial state of all parameters of a unit.
The units are delivered with this setting.
You can restore this initial state at any time by resetting the parameters
to the factory setting, thus canceling all parameter changes made since
the unit was delivered.
Grant parameter access
6: Parameter changes permitted via PMU and serial interface
SCom1 (OP1S and PC)
Select "Fixed settings" menu
Select desired factory setting
0: Standard
Note:
This parameter was correctly set prior to delivery of
the unit and only needs to be changed in exceptional
cases.
Start parameter reset
0: Parameter reset
1: No parameter change
Fig. 8-17
Sequence for parameter reset to factory setting
6SE7087-6KD50
Operating Instructions
SIMOVERT MASTERDRIVES
08.2009
Siemens AG