Functions
• During scaling, the gun closes several times with force.
• Before starting the scaling, the clamp must be referenced.
• In case of autoscaling out of order, a collective fault occurs if
Gun is not ready
•
Force deviation > 150 (limits adjustable)
•
8.12.2 Signals involved Autoscaler ok / not ok
• Enable positioning
• Start scaling
• Gun is referenced
• Ready signal Scaling
• Scaling ok
• Scaling not ok
• General error
Note: Signal diagrams can be provided after consultation.
8.13 Force test gun
Movements of the gun actuators!
Bruises possible!
Therefore, make sure that can be damaged by movements of the gun
actuators no one.
8.13.1 Functional description
• By setting the "Force test" input, the tongs make several closing movements
with point xx06 on the External force sensor.
• After the test procedure, the output "Force scaling ready message" is set and
the test result is put on the outputs "Scaling ok" or "Scaling not ok".
• The PRI7000 also displays the test result, the deviations of the force test are
displayed in the detailed diagnosis of the message.
8.13.2 Involved signals
• Force test
• Force scaling completed
• Scaling ok
• Scaling not ok
R911405944 | PRC 7x00-Lx/Wx-0200
CAUTION