6. Configuration
Characters,
factory setting
PV
P1
SV
0.0
PV
P2
SV
0.0
PV
Fc
SV
cn
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
OUT1 MV default value (MV manipulated variable)
OUT1 MV can be set, when "Preset 1 ON/OFF" or "Preset output 2 ON/
■
OFF" is selected in "Assignment DC current input".
Preset output 1 ON/OFF:
When there is a defect with the sensor input and no signal can be
determined, when event input is ON, the control is executed with the
preset MV
Preset output 2 ON/OFF:
When the event input is ON, the control is executed with the preset MV.
Setting: 0.0 ... 100.0 % (direct current output: -5.0 ... +105.0 %)
■
Availability:
■
CS6S: If event input has been ordered (options EVI, EXC, CT1/CT2)
CS6H, CS6L: If the serial interface (option RS-485) or event input (options
EVI, EXC, CT1/CT2) has been ordered
OUT2 MV default value
OUT2 MV can be set, when "Preset 1 ON/OFF" or "Preset output 2 ON/
■
OFF" is selected in "Assignment DC current input".
Preset output 1 ON/OFF:
When the sensor burns out during "Event input ON", the control is execut-
ed with the preset MV.
Preset output 2 ON/OFF:
When the event input is ON, the control is executed with the preset MV.
Setting: 0.0 ... 100.0 % (direct current output: -5.0 ... +105.0 %)
■
Available in the following cases:
CS6S: When event input EV2 (option EV2), heating/cooling control (option 3-term
■
control) or event input (options EVI, EXC, CT1/CT2) were ordered
CS6H, CS6L: When event input EV2 (option EV2), heating/cooling control (option
■
3-term control), serial interface (option RS-485) or event input (options EVI, EXC,
CT1/CT2) were ordered
When 019 (heating/cooling control relay output) in "Assignment of event output
■
EV2" is selected.
Controller/transmitter function
Select the controller or the convertor function
■
Controller
cnr
Transmitter
cn8
Only available when OUT1 is a direct current output.