6. Configuration
Characters,
factory setting
PV
rEF
SV
0.0
PV
c
SV
30
PV

SV
1.0
PV
oL
SV
100
PV
oLL
SV
0
PV
oAF
SV
0
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
Manual reset
Enables the manual reset
Setting range: Proportional range value
When a higher value than 100.0 % is set in "OUT1 proportional range",
the setting range is 100.0.
Only available for P and PD control.
OUT1 proportional cycle
Setting the cycle time for OUT1
Relay contact output: When the proportional cycle time is reduced, the
frequency of the relay action is increased and the life of the relay contact
is reduced.
Setting range: 0.5 or 1 ... 120 seconds
Not available for the direct current output type or when OUT1 is in "ON/OFF control".
OUT1 ON/OFF hysteresis
Setting the ON/OFF hysteresis for OUT1
Setting range: 0.1 ... 1,000.0 °C (°F)
DC voltage, current inputs: 1 ... 10,000
Not available when "OUT1" is in "ON/OFF control".
OUT1 upper limit value
Setting of the maximum output power for OUT1
Setting range: OUT1 lower limit up to 100 %
(direct current output type: OUT1 lower limit to 105 %)
Not available when "OUT1" is in "ON/OFF control".
OUT1 lower limit value
Setting the lower limit for OUT1
Setting range: 0 % OUT1 upper limit
(direct current output type: -5 % to OUT1 upper limit)
Not available when "OUT1" is in "ON/OFF control".
OUT1 gradients
Setting the changing value of OUT1 MV for 1 second
Setting range: 0 ... 100 % / second
Setting to 0 deactivates the function.
Not available when "OUT1" is in "ON/OFF control".