6. Configuration
Characters,
factory setting
PV
F2o
SV
00.00
PV
o
SV
1.000
PV
o
SV
0.0
PV
FL
SV
0.0
PV
cnL
SV
nonL
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
TS2 ON time
Setting the time signal output TS2 ON
■
Setting range: 00:00 to 99:59
■
Only available when 015 (time signal output) is selected in "Assignment event output
EV1".
Sensor correction coefficient
Setting the sensor correction coefficients
■
Setting the factor from the input value of the sensor
PV after sensor correction = current PV x (sensor correction coefficient) + (sensor
correction value)
Setting range: -10,000 ... +10,000
■
Sensor correction
Correction of the input value of the sensor
■
If the sensor cannot be placed exactly where a control is required, the
temperature measured by the sensor can deviate from the temperature at
the point controlled.
When several controllers are used, the measured temperatures someti-
mes do not match as a result of the sensor accuracy or the distribution
of the load capacities. In such a case, the control can be made at the
desired temperature through an adjustment of the input value of the
sensors.
PV after sensor correction = current PV x (sensor correction coefficient) + (sensor
correction value)
Setting range: -1,000.0 ... +1,000.0 °C (°F)
■
DC voltage, current inputs: -10,000 ... +10,000
PV filter time constant
Setting the time for the input filter
■
During the set time, an averaging of the actual value is carried out. If the
value is set too high, this can affect the control result due to the delay.
Setting range: 0.0 ... 10.0 seconds
■
Communication protocol
Select the communication protocol
■
WIKA protocol
nonL
Modbus ASCII
o
Modbus RTU
or
Only available when "serial interface" (option RS-485) is ordered.
EN
59