6. Configuration
Characters,
factory setting
PV
cc
SV
r
EN
PV
Pb
SV
10
PV
cb
SV
30
PV
b
SV
1
0
.
46
Selected object, functions, range
OUT2 cooling method
Select the OUT2 cooling method from air, oil or water cooling
OUT2 proportional band
Air cooling
SV
Selection: air cooling, linear characteristic

Oil cooling, 1.5 times linear characteristic
oL
Water cooling, 2 times linear characteristic
AF
Available when event output EV2 (option EV2) or heating/cooling control (option 3-term
control) has been ordered.
Not available when "OUT2" is in "ON/OFF control".
OUT2 proportional range
Setting the OUT2 proportional range
Setting range: 0 to input range °C (°F)
DC voltage, current inputs: 0.0 ... 1,000.0 %
OUT2 will become "ON/OFF control", if the setting is 0 or 0.0
Available when event output EV2 (option EV2) or heating/cooling control (option 3-term
control) has been ordered.
Not available when "OUT2" is in "ON/OFF control".
OUT2 proportional cycle
Setting the proportional cycle for OUT2
Relay contact output: When the proportional cycle time is reduced, the
frequency of the relay action is increased and the life of the relay contact
is reduced.
Setting range: 0.5 or 1 ... 120 seconds
Available when event output EV2 (option EV2) or heating/cooling control (option 3-term
control) has been ordered.
Not available for the direct current output type or when OUT2 is in "ON/OFF control".
OUT2 ON/OFF hysteresis
Setting the ON/OFF hysteresis for OUT2
Setting range: 0.1 ... 1,000.0 °C (°F)
DC voltage, current inputs: 1 ... 10,000
Available when event output EV2 (option EV2) or heating/cooling control (option 3-term
control) has been ordered.