6. Configuration
Characters,
factory setting
PV
1
SV
0
EN
PV
1
SV
0
48
Selected object, functions, range
EV1 limit value
Setting the EV1 limit value
Corresponds to "EV1 limit value" in the basic setting mode
EV1 achieves the lower limit value in the following cases:
When 004 (alarm output, independent of lower/upper limit value alarm),
006 (alarm output, independent of lower/upper limit range alarm) or 012 (alarm
output, independent of lower/upper limit value alarm with standby) is selected with
the "Assignment of event output EV1".
Upper limit value alarm
- (input range) to input range °C (°F)
Lower limit value alarm
- (input range) to input range °C (°F)
Upper/lower limit value alarm
0 to input range °C (°F)
Independent upper/lower limit value alarm
0 to input range °C (°F)
Upper/lower limit range alarm
0 to input range °C (°F)
Independent upper/lower limit range alarm
0 to input range °C (°F)
Deviation high alarm
Lower limit of input range to upper limit of input range
Minimum value alarm
Lower limit of input range to upper limit of input range
Upper limit value alarm with standby
- (input range) to input range °C (°F)
Lower limit value alarm with standby
- (input range) to input range °C (°F)
Upper/lower limit value alarm with standby alarm
0 to input range °C (°F)
Independent upper/lower limit value alarm with standby
0 to input range °C (°F)
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
EV1 upper limit value
Setting the upper limit value of EV1
Corresponds to "EV1 upper limit value" in the basic setting mode.
This is only possible in the following cases:
When 004 (alarm output, independent of lower/upper limit value alarm),
006 (alarm output, independent of lower/upper limit range alarm) or
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected with the "Assignment of event output EV1".
Setting range: Such as with "EV1 limit value"
WIKA operating instructions models CS6S, CS6H, CS6L