WIKA CS6S Betriebsanleitung Seite 31

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6. Configuration
Characters,
factory setting
PV
F2o
SV
00.00
PV
1
SV
00
and current
1
value CT1 are
displayed alter-
nately in the PV
display.
PV
2
SV
00
and current
2
value CT2 are
displayed alter-
nately in the PV
display.
PV
LP
SV
0
PV
LP
SV
0
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
TS2 ON time
Setting the time signal output TS2 ON
Setting range: 00:00 to 99:59
Only available when 015 (time signal output) is selected in "Assignment event output
EV1".
Heater burnout alarm 1
Setting the heater current value for the heater burnout alarm 1
and CT1 (current value) is displayed alternately in the PV display.
1
When OUT1 is set to ON, the current value CT1 will be set to the latest
value.
When OUT1 is set to OFF, the instrument stores the last value when
OUT1 was still ON.
Setting range:
20 A: 0.0 ... 20.0 A
100 A: 0.0 ... 100.0 A
Setting to 0.0 deactivates the alarm.
Not available for the direct current output type.
Available when the heater burnout alarm has been ordered.
Heater burnout alarm 2
Setting the heater current value for the heater burnout alarm 2
Only available for 3-phase operation
and CT2 (current value) is displayed alternately in the PV display.
2
When OUT1 is set to ON, the current value CT2 will be set to the latest
value.
When OUT1 is set to OFF, the instrument stores the last value when
OUT1 was still ON.
Setting range:
20 A: 0.0 ... 20.0 A
100 A: 0.0 ... 100.0 A
Setting to 0.0 deactivates the alarm.
Not available for the direct current output type.
Available when the heater burnout alarm has been ordered.
Control loop monitoring time
Defines the time for the control loop monitoring alarm
Setting range: 0 ... 200 minutes
Setting to 0 deactivates the alarm.
Control loop monitoring span
Defines the temperature for the control loop monitoring alarm
Setting range: 0 ... 150 °C (°F) or 0.0 ... 150.0 °C (°F)
DC voltage, current inputs: 0 ... 1,500
Setting to 0 deactivates the alarm.
EN
31