6. Configuration
Characters,
factory setting
PV
L
SV
1370
PV
LL
SV
200
PV
P
SV
0
PV
E8o1
SV
000
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
Scaling the upper limit value
Setting the end value
■
Range: Input range of the lower to the upper limit values of the scaling
■
Scaling the lower limit value
Setting the start value
■
Range: Input range of the lower to the upper limit values of the scaling
■
DC voltage, current inputs: -2,000 ... +10,000
Decimal point setting
Select the decimal point setting
■
No decimal point
0
0 1 figure after the decimal point
.
0
00 2 figures after the decimal point
.
0
000 3 figures after the decimal point
.
0
Only available for DC voltage and current input
Assignment of event output EV1
000 no result
001 Alarm output, upper limit value alarm
002 Alarm output, lower limit value alarm
003 Alarm output, upper/lower limit value alarm
004 Alarm output, independent upper/lower limit value alarm
005 Alarm output, upper/lower limit range alarm
006 Alarm output, independent upper/lower limit range alarm
007 Alarm output, deviation high alarm
008 Alarm output, minimum value alarm
009 Alarm output, upper limit value alarm with standby
010 Alarm output, lower limit value alarm with standby
011 Alarm output, upper/lower limit value alarm with standby
012 Alarm output, independent upper/lower limit value alarm with standby
013 Heater burnout alarm output
014 Control loop monitoring alarm output
015 Time signal output
During program control switching to OFF or ON, by the setting of OFF and ON
times within the program step
016 Output during AT
During AT, set to ON
017 End of program
Set to ON when the program has finished.
Acknowledge with the
018 Output during communications command
Set to OFF or ON through communications command 00E4H with serial interface
B0 EV1 output
0: OFF
1: ON
B1 EV2 output
0: OFF
1: ON
button.
EN