6. Configuration
Characters,
factory setting
PV
oL
SV
PV
oLL
SV
0
PV
b
SV
0
PV
coF
SV
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
OUT2 upper limit value
Setting the upper limit OUT2
■
Setting range: OUT2 lower limit up to 100 %
■
(direct current output type: OUT2 lower limit to 105 %)
Available when event output EV2 (EV2 option) or heating/cooling control (option 3-term
control) has been ordered.
OUT2 lower limit value
Setting the lower limit OUT2
■
Setting range: 0 % OUT2 upper limit
■
(direct current output type: -5 % to OUT2 upper limit)
Available when event output EV2 (EV2 option) or heating/cooling control (option 3-term
control) has been ordered.
Overlap band/deadband
Setting the overlap or dead band for control output 1 and 2
■
+ Settings: Deadband
- Settings: Overlap band
Setting range: -100.0 ... +100.0 °C (°F)
■
DC voltage, current inputs: -1,000 ... +1,000
Available when event output EV2 (EV2 option) or heating/cooling control (option 3-term
control) has been ordered.
Direct/Reverse acting
Select the reverse (heating) or direct (cooling) control program
■
Heating (indirect)
Cooling (direct)
cooL
EN