6. Configuration
Event input
When
■
001
follows:
When only event input Dl1 is selected.
EN
Storage space of the set value
DI1
When only event input DI2 is selected.
Storage space of the set value
DI2
When both event inputs DI1, DI2 are selected.
Storage space of the set value
DI1
DI2
Default value of
■
can be set in "OUT1, OUT2 MV default value" in the engineering mode.
When
■
00
"Auto/Manual control" in the "Assignment event input DI2" and the DI1-COM and
006
DI2-COM connections (closed) are switched at the same time, preset output 2 has
priority and the control starts with the MV, which has been set in the "OUT1/OUT2 MV
default value" in the engineering mode. In this case, the manual control is set and the MV
cannot be altered via the keyboard.
Signal clamping from OFF to ON or ON to OFF will be triggered.
■
When
008
the action ON (closed) or OFF (open) is executed. The instrument must be switched on
for this.
Example: Model CS6S
Controller status
Connections 17 - 18
"DI1-COM" ON (closed)
Connections 17 - 18
"DI1-COM" OFF (open)
36
(set point memory) is selected, the memory of the set value appears as
(preset output 1 ON/OFF) and
004
(preset output 2 ON/OFF) is selected in the "Assignment event input DI1",
"Program control RUN/STOP" is selected in "Assignment event input DI1",
Standby mode
17 - 18 "DI1-COM":
OFF (open)
Standby mode
Program control will be executed when
"17-18 DI1-COM" changes from OFF
(open) to ON (closed).
SV1
Open
SV1
Open
SV1
SV2
Open
Closed
Open
Open
005
Program control
17 - 18 "DI1-COM":
ON (closed)
Program control
WIKA operating instructions models CS6S, CS6H, CS6L
SV2
Closed
SV2
Closed
SV3
SV4
Open
Closed
Closed
Closed
(preset output 2 ON/OFF)
Program control STOP
(standby mode)
17 - 18 "DI1-COM":
OFF (open)
Program control stopped
Program control will be stopped when "17-
18 DI1-COM" changes from ON (closed)
to OFF (open).