6. Configuration
Characters,
factory setting
PV
n
SV
LocL
PV
rL
SV
1370
PV
rLL
SV
200
PV
rb
SV
0
PV
o
SV
P8
PV
L
SV
1370
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
Remote control/local
Select remote (remote control operation) or local (keyboard operation)
setting of the SV
Local
LocL
Remote control
n
Only available when "External regulated input" (EXC option) has been ordered.
External regulated input, upper limit value
Setting the upper limit of the external regulated input
(This value corresponds to 20 mA in the DC current input.)
Setting range: Lower limit of the external regulated input up to the upper
limit of the input range
Only available when "External regulated input" (EXC option) has been ordered.
External regulated input, lower limit value
Setting the lower limit of the external regulated input
(This value corresponds to 4 mA in the DC current input.)
Setting range: Upper limit value of the external regulated input up to the
lower limit of the input range
Only available when "External regulated input" (EXC option) has been ordered.
Remote bias
With the remote operation, the SV includes the remotely controlled bias value.
Setting range: Converted value of ±20 % of the input range
DC voltage, current inputs: ±20 % of the scaling span
Only available when "External regulated input" (EXC option) has been ordered.
Transmit output type
Select the transmit output type
Changing the transmit output type
PV transmission
8
SV transmission
8
MV transmission
n8
DV transmission
8
Only available when "Transmit output" (EXC option) has been ordered.
Transmit output upper limit value
Setting the upper limit of the transmit output
(This value corresponds to 20 mA in the direct current output.)
PV, SV transmission
MV transmission
DV transmission
Only available when "Transmit output" (EXC option) has been ordered.
Lower limit value of the transmit output up to the upper
limit value of the input range
Transmit output lower limit to 105.0 %
Lower limit value of the transmit output up to the
scaling span