6. Configuration
Characters,
factory setting
PV
2
SV
0
PV
2
SV
0
PV
1
SV
0
0
.
and current
1
value CT1
is displayed
alternately in
the PV display.
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
EV2 limit value
Setting the limit value for EV2
Corresponds to "EV2 limit value" in the basic setting mode.
The lower limit value, EV2, is reached in the following cases:
When 004 (alarm output, independent of lower/upper limit value alarm),
006 (alarm output, independent of lower/upper limit range alarm) or
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected with the "Assignment of event output EV2".
Setting range: Such as with "EV1 limit value"
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV2".
EV2 upper limit value
Setting the upper limit value of EV2
Corresponds to "EV2 upper limit value" in the basic setting mode.
This is only possible in the following cases:
When 004 (alarm output, independent of lower/upper limit value alarm),
006 (alarm output, independent of lower/upper limit range alarm) or
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected with the "Assignment of event output EV2".
Setting range: Such as with "EV1 limit value"
Heater burnout alarm 1
Setting the heater current value for the heater burnout alarm 1
Corresponds to "Heater burnout alarm 1" in the basic setting mode.
and CT1 (current value) is displayed alternately in the PV display.
1
When OUT1 is set to ON, the current value CT1 will be set to the latest
value.
When OUT1 is set to OFF, the instrument stores the last value when
OUT1 was still ON.
Setting range:
20.0 A:
100.0 A: 0.0 ... 100.0 A
Setting to 0.0 deactivates the alarm.
Only available when the heater burnout alarm has been ordered (options RS-485, EIV,
CT1/CT2).
0.0 ... 20.0 A