6. Configuration
Characters,
factory setting
PV
A1
SV
0
PV
A1
SV
1.0
PV
A1
SV
0
PV
A1Ln
SV
nonL
PV
F1
SV
1
PV
F1
SV
00.00
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
EV1 upper limit value
Setting the upper limit value of EV1
■
Only possible in the following cases:
■
When 004 (alarm output, independent of lower/upper limit value alarm),
006 (alarm output, independent of lower/upper limit range alarm) or
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected with the "Assignment of event output EV1".
Range: Such as with "EV1 limit value"
■
EV1 alarm hysteresis
Setting the EV1 alarm hysteresis
■
Setting range: 0.1 ... 1,000.0 °C (°F)
■
DC voltage, current inputs: 1 ... 10,000
Available when an alarm from 001 (alarm output, upper limit value alarm) to 012
(alarm output, independent of lower/upper limit value alarm with standby) is selected in
the "Assignment of event output EV1".
EV1 alarm delay time
Setting the EV1 alarm delay time
■
When the response time has elapsed, after the input has reached the
■
alarm output range, the alarm is activated.
Setting range: 0 ... 10,000 seconds
■
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
EV1 switch behaviour alarm
Select the status live/volt-free for the EV1 alarm
Open
nonL
Closed
E8
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
TS1 output program step
Setting the program step, at which the time signal output TS1 will be
■
switched on or off during the program control
Setting range: 1 ... 9
■
Only available when 015 (time signal output) is selected in "Assignment event output
EV1".
TS1 OFF time
Setting the time signal output TS1 OFF
■
Setting range: 00:00 to 99:59
■
Only available when 015 (time signal output) is selected in "Assignment event output
EV1".