WIKA CS6S Betriebsanleitung Seite 37

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6. Configuration
Time signal output
The time signal output will be activated during the ON time, within the step, to which the
step number has been set.
The ON time follows the OFF time of the time signal output, after the program control has
been started.
The following table shows that the temperature within an hour rises to 200 °C and for a
further two hours remains at 200 °C, after the program control has been started.
Step
Step SV
Step time
Time signal output will be displayed as follows.
TS1/TS2 output program step: 2
TS1/TS2 OFF time: 30 minutes
TS1/TS2 ON time: 1 hour
Step
200 °C
0 °C
ON
Time signal output
OFF
The time signal output shows the action of the "TS1/TS2 output program step".
Example: When the TS1/TS2 ON time is set above to "2:00", the time signal output will be
switched as soon as step 2 has ended.
WIKA operating instructions models CS6S, CS6H, CS6L
1
2
200 °C
200 °C
1 hour
2 hours
1
1:00
00:30
Program control
OFF time
2
2:00
1:00
ON time
EN
37