6. Configuration
Characters,
factory setting
PV
A1
SV
1.0
PV
A1
SV
0
PV
A1Ln
SV
nonL
PV
F1
SV
1
PV
F1
SV
00.00
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
EV1 alarm hysteresis
Setting the EV1 alarm hysteresis
■
Setting range: 0.1 ... 1,000.0 °C (°F)
■
DC voltage, current inputs: 1 ... 10,000
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
EV1 alarm delay time
Setting the EV1 alarm delay time
■
Corresponds to "EV1 alarm delay time" in the basic setting mode
When the response time has elapsed, after the input has reached the
■
alarm output range, the alarm is activated.
Setting range: 0 ... 10,000 seconds
■
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
EV1 alarm live/volt-free
Select the status live/volt-free for the EV1 alarm
■
Corresponds to "EV1 alarm live/volt-free" in the basic setting mode
Live
nonL
Volt-free
E8
Available when an alarm from 001 (alarm output, upper limit value alarm) to
012 (alarm output, independent of lower/upper limit value alarm with standby) is
selected in the "Assignment of event output EV1".
TS1 output program step
Setting the program step, at which the time signal output TS1 will be
■
switched on or off during the program control
Setting range: 1 ... 9
■
Only available when 015 (time signal output) is selected in "Assignment event output
EV1".
TS1 OFF time
Setting the time signal output TS1 OFF
■
Corresponds to "TS1 OFF time" in the basic setting mode
Setting range: 00:00 to 99:59
■
Only available when 015 (time signal output) is selected in "Assignment event output
EV2".
EN