6. Configuration
6.4 Secondary setting mode
+
(press in this order and hold
together for 3 s)
EN
or
Clarification of the setting items
Characters,
factory setting
PV
SV
PV
SV
10
PV
1
SV
200
PV
SV
50
PV
Ar
SV
50
44
from the RUN mode:
Selecting the secondary setting mode
Select the relevant setting item
Saving the set data
Selected object, functions, range
Auto-tuning AT/auto-reset execute/delete
Select:
■
- "AT" or "AT with commissioning"
- "Execute/delete" in the "PID control"
- "Auto-reset execute/delete" in the "P control program" or "PD control
program"
AT/AT with commissioning/auto-reset delete
Execute "AT"
Execute "AT with commissioning"
r Execute "Auto-reset"
Only available for "ON/OFF control" or "PI control".
OUT1 proportional band
Setting range: 0 to input range °C (°F)
■
DC voltage, current inputs: 0.0 ... 1,000.0 %
OUT1 will become "ON/OFF control", if the setting is 0 or 0.0
Integral time
"Auto-reset" can be executed when "PD control program" (I = 0)
■
Setting range: 0 ... 3,600 seconds
■
When the value is set to 0, the integral behaviour is deactivated.
Not available when "OUT1" is in "ON/OFF control".
Derivative time
Setting range: 0 ... 1,800 seconds
■
When the value is set to 0, the derivative time is deactivated.
Not available when "OUT1" is in "ON/OFF control".
ARW (anti-reset windup) parameter
Setting the ARW (anti-reset windup)
■
Setting range: 0 ... 100 %
■
Only available for "PID control".
WIKA operating instructions models CS6S, CS6H, CS6L