6. Configuration
Characters,
factory setting
PV
5
SV
0
PV
5
SV
00.00
PV
5
SV
0
PV
6
SV
0
PV
6
SV
00.00
PV
6
SV
0
WIKA operating instructions models CS6S, CS6H, CS6L
Selected object, functions, range
Step 5: SV
Setting SV5
■
Setting range: Scaling lower to upper limit value
■
Only available when program control in "ON/OFF main function" (see chapter 6.5
"Engineering mode") is selected.
Step 5: Time
Setting the time of step 5
■
Setting range:
■
When
is set, step 5 is paused and the fixed value control is
executed through use of the "Step 5: SV".
Only available when program control is selected in "ON/OFF main function" (see
chapter 6.5 "Engineering mode").
Step 5: Dwell time
Setting the delay time of step 5
■
Setting range: 0 to the converted value of 20 % of the input range
■
DC voltage, current inputs: 0 to converted value of 20 % of the scaling
span
Setting to 0 deactivates the delay function.
Only available when program control in "ON/OFF main function" (see chapter 6.5
"Engineering mode") is selected.
Step 6: SV
Setting SV6
■
Setting range: Scaling lower to upper limit value
■
Only available when program control in "ON/OFF main function" (see chapter 6.5
"Engineering mode") is selected.
Step 6: Time
Setting the time of step 6
■
Setting range:
■
When
is set, step 6 is paused and the fixed value control is
executed through use of the "Step 6: SV".
Only available when program control in "ON/OFF main function" (see chapter 6.5
"Engineering mode") is selected.
Step 6: Dwell time
Setting the delay time of step 6
■
Setting range: 0 to the converted value of 20 % of the input range
■
DC voltage, current inputs: 0 to converted value of 20 % of the scaling
span
Setting to 0 deactivates the delay function.
Only available when program control in "ON/OFF main function" (see chapter 6.5
"Engineering mode") is selected.
or 00:00 ... 99:59
or 00:00 ... 99:59