12. Demand control
Set when there is demand control.
Adjust terminal voltage within 1 ~ 10 V to change the operating current limit.
(NOTE) Does not display when there is no Optional PCB.
Analog input
Rate
[v]
[%]
0.0
not activate
0.1 ~ 0.6
0.7
10
activate
0.8
0.9 ~ 1.1
10
1.2
15
1.3
1.4 ~ 1.6
15
1.7
20
1.8
1.9 ~ 2.1
20
2.2
25
2.3
2.4 ~ 2.6
25
2.7
30
2.8
2.9 ~ 3.1
30
3.2
35
3.3
3.4 ~ 3.6
35
3.7
40
3.8
13. SG ready
Switch operation of heat pump by open-short of 2 terminals.
Setting belows are possible
SG signal
Vcc-bit1
Vcc-bit2
Open
Open
Normal
Short
Open
Heat pump and Heater OFF
Open
Short
Capacity 1
Short
Short
Capacity 2
Capacity setting 1
- DHW capacity ___%
- Heating capacity ___%
- Cooling capacity ___°C
Capacity setting 2
- DHW capacity ___%
- Heating capacity ___%
- Cooling capacity ___°C
(When SG ready set to YES, Bivalent control pattern will set to Auto.)
14. External Compressor SW
Set when external compressor SW is connected.
SW is connected to external devices to control power consumption, Open Signal will
stop compressor's operation. (Heating operation etc. are not cancelled).
(NOTE) Does not display if there is no Optional PCB.
If follow Swiss standard power connection, need to turn on DIP SW (SW2 pin3) of main
unit PCB. Short/Open signal used to ON/OFF tank heater (for sterilization purpose)
26
Initial setting: No
Analog input
[v]
3.9 ~ 4.1
4.2
45
4.3
not
4.4 ~ 4.6
4.7
50
4.8
10
4.9 ~ 5.1
5.2
55
5.3
15
5.4 ~ 5.6
5.7
60
5.8
20
5.9 ~ 6.1
6.2
65
6.3
25
6.4 ~ 6.6
6.7
70
6.8
30
6.9 ~ 7.1
7.2
75
7.3
35
Initial setting: No
Working pattern
Set by SG ready setting of remote controller
Initial setting: No
System setup
Rate
Analog input
[%]
[v]
40
7.4 ~ 7.6
7.7
40
7.8
45
7.9 ~ 8.1
8.2
45
8.3
50
8.4 ~ 8.6
8.7
50
8.8
55
8.9 ~ 9.1
9.2
55
9.3
60
9.4 ~ 9.6
9.7
60
9.8
65
9.9 ~
65
*A minimum operating current is applied on each model for
protection purpose.
70
*0.2 voltage hysteresis is provided.
*The value of voltage after 2nd decimal point are cut off.
70
System setup
System setup
External SW
Solar connection
External error signal
Demand control
Select
Confi rm
Rate
[%]
75
80
75
80
85
80
85
90
85
90
95
90
95
100
95
100
Solar connection
External error signal
Demand control
SG ready
Select
Confi rm
External error signal
Demand control
SG ready
External compressor SW
Select
Confi rm