8.3 Starting up the Pressure Zone

The pumps start automatically 5 seconds after the supply
voltage is connected.
If the solution is delivered with iGRID Cloud, the setpoint
must be set in the iGRID Portal before starting any pump.
1. Make sure that the main valves are open.
2. Connect the mains supply voltage to the main pump or pumps
and the drainage pump.
3. Adjust the setpoint to the desired operating pressure via the
operating panel of the pump or via Grundfos GO Remote.
See the installation and operating instructions of the pump.
4. Check the operating panel for any alarms and warnings.
See the installation and operating instructions of the pump.

8.4 Starting up the Temperature Zone

The pumps start automatically 5 seconds after the supply
voltage is connected.
If the solution is delivered with iGRID Cloud, the setpoint
must be set in the iGRID Portal before starting any pump.
1. Make sure that the main valves are open.
2. Connect the mains supply voltage to the main pump or pumps
and to the drainage pump.
3. Adjust the setpoint to the desired operating temperature via the
operating panel of the pump or via Grundfos GO Remote.
See the installation and operating instructions of the pump.
4. Check the operating panel for any alarms and warnings.
See the installation and operating instructions of the pump.

8.5 Completing installation work at the solution

Make sure that the cover is properly closed. Check and remove
foreign bodies, if any.
The cover and the locking device must be operated by the same
person.
The cover and the locking device must only be used when no
persons are in the pit.
WARNING
Fall hazard
Death or serious personal injury
Make sure that the cover is properly closed and locked
when work in the pit iscompleted.

9. Servicing the solution

Check the pump or pumps and the drainage pump
for functionality and tightness.
We recommend that the pump or pumps and the drainage
pump are checked at least once a year.
WARNING
Risk of scalding
Death or serious personal injury
Disconnect the mains supply in the event of
steam releasedue to a leak.
Open the drain valves slowly to release pressure when
draining the pump or pumps.
WARNING
Risk of scalding
Death or serious personal injury
Make sure that the system has been cooled down
when working on uninsulated pipe sections or similar.
Make sure that the system is drained slowly.
Use only the ladder and the pit floor when you use the
pit.
Close the main valves before carrying out any work on
hydraulic parts. Make sure that the main valves are in
a completely closed position and that the lock is
engaged.
WARNING
Risk of scalding
Death or serious personal injury
Use personal protective equipment according to local
regulations when you install the insulating pads.
DANGER
Slippery surface
Death or serious personal injury
Use personal protective equipment.
WARNING
Electric shock
Death or serious personal injury
Disconnect the power supply before starting any
electrical work or in the event of the solution being
flooded. Lock the supply disconnecting device to avoid
unintentional reconnection.
Follow the instructions in the service instructions for
the pump and motor.
Do not clean the solutionwith a high-pressure cleaner.
Make sure that any control panels and internal pipe
installations are connected to earth.
WARNING
Risk of being hit by a vehicle
Death or serious personal injury
Make sure to mark off the area around
the solution when working in the pit.
Follow local regulations when working at the solution.
DANGER
Fall hazard
Death or serious personal injury
Make sure to mark off the area around the solution.
Follow local regulations when working at the solution.
WARNING
Fall hazard
Death or serious personal injury
Stand in the pit when you carry out work in the pit.
CAUTION
Hot surface
Minor or moderate personal injury
Use personal protective equipment when working at
the solution.
15