9.2.7 Lubrication status of motor bearings (only 11-22 kW)

This display shows how many times the motor bearings have
been relubricated and when to replace the motor bearings.
When the motor bearings have been relubricated, confirm this
action in the INSTALLATION menu. See 9.3.8 Confirming
relubrication/replacement of motor bearings (only 11-22 kW).
When relubrication is confirmed, the figure in the above display
will be increased by one.

9.2.8 Time till relubrication of motor bearings (only 11-22 kW)

This display shows when to relubricate the motor bearings.
The controller monitors the operating pattern of the pump and
calculates the period between bearing relubrications. If the
operating pattern changes, the calculated time till relubrication
may change as well.
The displayable values are these:
in 2 years
in 1 year
in 6 months
in 3 months
in 1 month
in 1 week
Now!

9.2.9 Time till replacement of motor bearings (only 11-22 kW)

When the motor bearings have been relubricated, a prescribed
number of times stored in the controller, the display in section
9.2.8 will be replaced by the display below.
This display shows when to replace the motor bearings. The
controller monitors the operating pattern of the pump and
calculates the period between bearing replacements.
The displayable values are these:
in 2 years
in 1 year
in 6 months
in 3 months
in 1 month
in 1 week
Now!
24

9.3 Menu INSTALLATION

9.3.1 Control mode

Select one of the following control modes (see fig. 24):
Prop. pressure (proportional pressure)
Const. pressure (constant pressure)
Const. curve (constant curve).
How to set the desired performance, see section 9.1.1 Setpoint.
If the pump is connected to a bus, the control
mode cannot be selected via the R100. See
Note
section 14. Bus signal.

9.3.2 External setpoint

The input for external setpoint signal can be set to different signal
types.
Select one of the following types:
0-10 V
0-20 mA
4-20 mA
Not active.
If Not active is selected, the setpoint set by means of the R100 or
on the control panel will apply.
If one of the signal types is selected, the actual setpoint is
influenced by the signal connected to the external setpoint input,
see 13. External setpoint signal.

9.3.3 Signal relay (only 11-22 kW)

Pumps of 11-22 kW have two signal relays. Signal relay 1 is
factory set to Alarm and signal relay 2 to Warning.
In the displays below, select in which one of three or six operating
situations the signal relay should be activated.
11-22 kW
Ready
Alarm
Operation
Pump running
Warning
Relubricate.
Fault and Alarm cover faults resulting in Alarm.
Warning covers faults resulting in Warning.
Note
Relubricate covers only that one individual event.
For distinction between alarm and warning, see
section 9.1.3 Fault indications.
For further information, see section 16. Indicator lights and signal
relay.
11-22 kW
Ready
Alarm
Operation
Pump running
Warning
Relubricate.