Installation
Notes:
• Installation must only be performed by qualified personnel, and in accordance with local
governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding procedures.
All field wiring must have insulation suitable for at least 250V.
Hazardous voltages present on transducer terminals during operation.
DC input terminals shall be supplied from a source providing electrical isolation
between the input and output, in order to meet applicable safety requirements of
IEC 61010-1.
• Relay contact terminals are for use with equipment that has no accessible live parts and
wiring that has insulation suitable for at least 250 V. The maximum allowable working volt-
age between adjacent relay contacts shall be 250 V.
• The non-metallic enclosure does not provide grounding between conduit connections.
Use grounding type bushings and jumpers.

Mounting instructions

Mounting instructions differ for wall, pipe, DIN-rail, and remote display panel mount devices.
Please follow the specific instructions for your device.
When routing cable through a conduit, please follow the Cable Routing
Note:
instructions on page 9 before mounting the SITRANS LUT400.
Wall or panel mount
All configurations of the SITRANS LUT400 are shipped with a mounting back plate. The panel
mount model comes with both a LUI display and a blank lid.
enclosure with optional display lid
Note: Wall mount fasteners not included.
Page EN-4
SITRANS LUT400 (HART)
mounting back plate
7ML19985XU81
clips (2 places)
clips (2 places)