Connecting HART
mA Output (HART)
For ACTIVE HART
connection (using
LUT400 integral power
supply), connect
terminals 22 and 23.
For more information, consult the mA output parameters (
reference section of the full Operating Instructions.

Connecting in hazardous area installations

See page 35.
Commissioning SITRANS LUT400
We recommend that you configure your application in the following order:
• First, run the appropriate Quick Start Wizard for your application (Level, Volume, Flow).
• Next, setup pumps via the Pump Control Wizard (if applicable).
• Lastly, configure alarms, or other controls, totalizers and samplers, referencing the
respective parameters (see full Operating Instructions).
There are two ways to access the Quick Start Wizards:
Quick Start Wizards via LUI
• locally (see
• from a remote location (see
Activating SITRANS LUT400
Power up the device. SITRANS LUT400 automatically starts up in Measurement mode. A
transition screen showing first the Siemens logo and then the current firmware revision of the
LUI is displayed while the first measurement is being processed.
The first time the device is configured, you will be prompted to select a language (English,
German, French, Spanish or Chinese).
The correct date and time should be set prior to configuring the device. (To modify, set
2.14.Date and Time
parameter
Page EN-14
mA OUT/HART
22
23
PAS
ACT
on page 17)
Other Quick Start Wizards:
. See full Operating Instructions for details.)
SITRANS LUT400 (HART)
For PASSIVE HART
connection (using
external power
24
supply), connect
terminals 23 and 24.
2.5.Current Output
on page 17)
) in the parameter
7ML19985XU81