Maximum Volume
The maximum volume of the vessel. Enter the vessel volume corresponding to the
High Calibration Point. For example, if your maximum vessel volume is 8000 L, enter a
value of 8000.
Value
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
Options
To transfer Quick Start values to the device and return to Program menu, press
DOWN arrow
Measurement mode.
1.1.3. QS Flow
Use this wizard to configure simple flow applications.
[Visible on LUT430 (Pump and Flow), and LUT440 (OCM) configured models only.]
a) Press RIGHT arrow
MENU.
b) Press RIGHT arrow
c) Press DOWN arrow
d) At each step, press DOWN arrow
accept default values and move directly to the
next item, 
or RIGHT arrow
current selection is highlighted.
e) Scroll to desired item and press RIGHT arrow
to store the change, then press DOWN
arrow
to continue.
f)
At any time, you can press UP arrow
go back, or LEFT arrow
Start of QS Flow Wizard
Shows the type of Wizard to be executed.
Options
7ML19985XU81
Range: 0.0 to 9999999
Default: 100.0
BACK, CANCEL, FINISH (Display returns to 1. 1 Quick Start menu when Quick
Start is successfully completed or cancelled. If CANCEL is selected, no
changes are written to the device.)
(Finish). Then press LEFT arrow
to activate PROGRAM mode and open menu level 1: MAIN
two times to navigate to menu item 1.1.1.
two times and RIGHT arrow
to open Edit mode: the
to cancel the wizard.
CANCEL, START
SITRANS LUT400 (HART)
three times to return to
to open QS Flow.
to
QUICK START FLOW
QUICK START FLOW
TRANSDUCER
NO TRANSDUCER
XRS-5
XPS-10
XPS-15
XCT-8
XCT-12
to
TRANSDUCER
XRS-5
BACK
CANCEL
EDIT
NEXT
Page EN-23