c) Select the program for the exhaust gas analy-
sis on the device and switch on the measuring
device.
d) Starting the device.
 The burner starts.
e) Wait for the calibration phase of the burner
(duration: 5 minutes).
f) Insert the measuring probe through the bore-
hole in the exhaust pipe.
g) Start the measurement on the measuring de-
vice.
 The values are output on the measuring
device and can be read.
h) Use the table below to check whether the ex-
haust gas values are within the limits.
i) Adjust the burner if necessary.
j) Carry out a soot measurement using the soot
pump (article no. 4000000).
 You 'have completed the exhaust analysis.
NOTICE
The values of the exhaust gas analysis for heating
oil EL should be -12.5 % CO² and -4 % residual
oxygen.
NOTICE
If the specified exhaust gas values are not
achieved, the burner settings must be readjusted.
Exhaust gas limit values
For Germany: Regulated in BImSchG, status
26/01/2010 § 1 and § 8.
EN
Oil heater K 120 (R) / K 160 (R)
Nominal heat-
Soot index
ing output in
kW
>4 <25
1
>25 <50
1
>50
1
Tab. 17:
Permissible exhaust gas limit values in Germa-
ny
Exception: The measurement must be carried out
3 months after the initial commissioning.
For Austria: Regulated in the regional provisions of
the LHKG 2008.
Nominal heat-
Soot index
ing output in
kW
>4
1
>4 <10
1
>10
1
Tab. 18:
Permissible exhaust gas limit values in Austria
Nominal heat-
Soot
CO
ing output in
index
content
kW
>350
1
max. 20
mg/MJ
Tab. 19:
Permissible exhaust gas limit values in Austria
(Burgenland), by nominal heating output
Exceptions:
– The NO
limit value applies only to wood com-
X
bustion systems (35 mg/MJ).
– The NO
limit value must not be exceeded by
X
more than 100 % for instantaneous water
heaters, storage water heaters and individual
furnaces.
Max. exhaust
gas losses in %
11
10
9
Max. exhaust
gas losses in %
22
19
16
NO
content
x
70 mg/MJ (max.
252.80 mg/kWh)
75 / 85

Werbung

loading

Diese Anleitung auch für:

K 120 rK 160K 160 r