The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Fig. 11-2
The date of manufacture can be derived as follows:
Character
U
V
W
X
Table 11-2
6SE7087-6KN50
Operating Instructions
manuals search engine
x Derating
altitude
Altitude: 3000 m
Ambient temperature: 35 °C
⇒ Total derating = 0.845 x 1.125 = 0.95
Rating plate
Year of manufacture:
Character
2006
1 to 9
2007
2008
2009
Assignment of characters to the month and year of manufacture
Technical Data
ambient temperature
K
= 0.845
1
K
= 1.125
2
Unit designation
List of unit options
Year of manufacture
Month of manufacture
Month of manufacture
January to September
O
October
N
November
D
December
11-3