06.2006
Order
number
6SE70...
31-0TE 0
31-2TF 0
31-8TF 0
32-1TG 0
32-6TG 0
33-2TG 0
33-7TG 0
35-1TJ 0
36-0TJ70
37-0TJ70
38-6TK70
41-1TK70
41-3TL70
NOTES
Siemens AG
SIMOVERT MASTERDRIVES
Downloaded from
www.Manualslib.com
Rated
Infeed side
direct Cross-section
current VDE
AWG
[A]
[A]
[mm²]
110
1x70
1x000
160 3224
148
2x35
2x0
250 3227
184
2x35
2x0
250 3227
208
2x50
2x00
315 3230-0B 3720
254
2x70
2x000
450 3233
312
2x95
2x4/0
450 3233
367
2x120 2x300
500 3334-0B 6710
503
4x300 4x800
450 2x3233
702
4x800
560 2x3335
4x300
821
4x800
560 2x3335
4x300
1023
4x800
710 2x3337-8
4x300
1310
6x800
800 2x3337-8
6x300
1551
6x800
900 2x3340
6x300
AWG: American Wire Gauge
= 5 corresponds to MASTERDRIVES Motion Control
= 7 corresponds to MASTERDRIVES Motion Control Performance 2
Table 7-1
• The connection cross-sections are determined for copper cables at
40 °C (104 °F) ambient temperature and cables with a permissible
operating temperature at the conductor of 70 °C (in accordance with
DIN VDE 0298-4 / 08.03).
• If DC fuses are integrated, additional fuses are not necessary on the
infeed side provided that the connecting cables to the DC bus are
laid short-circuit-proof and that there is no risk of the cables being
overloaded by other consumers.
The fuses are integrated in units of type J.
The fuses are an option (L30) on units of types E, F and G.
• The connecting lengths to the rectifier unit - also between inverters
on systems - need to be kept as short as possible. Ideally, these are
executed as low-inductance bus bars.
6SE7087-6KN50
Operating Instructions
manuals search engine
Recommended fuse
Type
North America
3NE
170M
[V]
[A]
3718
600
350
3718
660
350
3718
660
350
660
450
6709
660
550
6709
660
550
660
630
660
550
2x6709
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Cross-sections, fuses
Connecting-up
Motor side
Rated output
Cross-section
voltage
current VDE
AWG
[V]
[A]
[mm²]
0 to 480
92
1x35
1x0
0 to 480
124
2x25
2x2
0 to 480
155
2x35
2x0
0 to 480
175
2x35
2x0
0 to 480
218
2x50
2x00
0 to 480
262
2x70
2x000
0 to 480
308
2x95
2x4/0
0 to 480
423
2x300 2x800
0 to 480
590
4x300 4x800
0 to 480
690
4x300 4x800
0 to 480
860
4x300 4x800
0 to 480
1100
4x300 4x800
0 to 480
1300
4x300 4x800
7-5