Commissioning
The most important codes for commissioning
Code
No.
Name
C0088
Rated motor
current
C0089
Rated motor
frequency
C0090
Rated motor
voltage
C0091
Motor cos ϕ
C0119
Configuration
of motor
temperature
-13-
monitoring
(PTC input) /
earth fault
detection
C0140*
Additive
frequency
setpoint
(NSET1-NADD)
NOU
Possible settings
Lenze
Selection
0.0
50
10
50
0.40
0
0
PTC input not
active
1
PTC input
active,
TRIP set
2
PTC input
active,
Warning set
3
PTC input not
active
4
PTC input
active,
TRIP set
5
PTC input
active,
Warning set
0.00 -650.00
EDK82MV222 DE/EN/FR 9.0
{0.1 A}
650.0
{1 Hz}
960
{1 V}
500
{0.1}
1.0
Earth fault
detection active
Earth fault
detection
inactive
{0.02
650.00
Hz}
IMPORTANT
Depending on the controller
0.0 ... 2.0 x rated output
current of the controller
230 V with 230 V
controllers,
400 V with 400 V
controllers
Depending on the controller
Signal output
configuration under
C0415
If several parameter sets
are used, the monitoring
must be separately
adjusted for each
parameter set.
Deactivate the earth fault
detection, if it has been
activated unintentionally.
If the earth fault detection
is active, the motor starts
after controller enable
with a delay of approx.40
ms.
Selection via function
 of the keypad or the
parameter channel
Is added to main setpoint
Value is stored when
switching the mains or
removing the keypad
L